Scale parameters and functions
8.27 DR 30 Process state
SIWAREX WP251
140 Manual, 12/2015, A5E37203357A
Gross, net and tare process values
These are the gross, net and tare weights in high-resolution process form.
Gross, net and tare weights
These are the gross, net and tare weights after rounding and filtering defined in data record
3.
This is the gross/net weight after rounding according to settings in data record 3 and a
resolution raised by a factor of 10.
Gross/Net process weight 2
These are the high-resolution, internal process values of the gross and net weight after
filtering according to the settings in data record 24.
Measured values are re-calculated every 10 ms in the SIWAREX module. The refresh
counter is also incremented by 1 each time. When the counter reaches the value 65536, it is
reset. The counter can be used as a time stamp for data record DR 30.
Actual weight of last dosing
This parameter shows the last dosed (net) weight.
Totalizer 1 and Totalizer 2
These are two sum memories that can be reset separately via a command (Reset totalizer 1
(651), Reset totalizer 2 (652)). In NAWI and catchweigher modes, the dosed weight is added
to the sums after the tolerance check. In gravimetric filling mode, the actual weight
determined by the tolerance check in checked cycles is summed. For cycles without
tolerance check, the set point set in DR 20 is included in the calculated sums.