Scale parameters and functions
8.3 DR 3 Calibration parameters
SIWAREX WP251
72 Manual, 12/2015, A5E37203357A
Image 8-1 Standstill monitoring
8.3.22
Standstill 1 - range
This parameter defines the weight range (+/- around the current weight) by which the weight
may fluctuate within Standstill time 1, in order to determine that standstill has occurred. The
setting is made in numerical increments (d).
8.3.23
Standstill 1 - time
This parameter defines the time window in which the weight value may fluctuate within
Standstill range 1 only, in order to determine that standstill has occurred. The setting is made
in milliseconds (ms).
8.3.24
Max. waiting time for standstill 1
The maximum waiting time for standstill 1 applies when a command is performed that is
dependent on the occurrence of standstill 1. A technology message is generated if the
command could not be executed during the waiting time because there is no standstill.