heat Pu mP integration
Default: Inactive
Setting range: Active, Inactive
This menu is hidden and only available to Base PRO
systems with less than 5 controllers. To access the menu,
press and hold the menu title “Integration” on top of the
screen until this submenu appears.
This function is only available in selected countries,
contact a local Uponor office for more information.
Caution!
If Heat pump integration is deactivated
make sure that it also is deactivated in the
heat pump. Otherwise it may affect the
operation of the heat pump.
When activated, the system will provide the heat pump
with temperature sensor data from Uponor system
thermostats to adjust the supply temperature. Device
integration specific settings also appears.
Dynamic heat curve:
Default: Inactive
Setting range: Active, Inactive
Activates dynamic adjustment of the system heat curve.
Response:
Default: Slow
Setting range: Slow, Moderate, Fast
Set the response speed of the system.
A slow system takes longer to reach the setpoint, a fast
system is faster but might overshoot the setpoint, and a
moderate system is somewhere in between.
Pulse input:
Default: Inactive
Setting range: Inactive, Active
Activate pulse input on the controller.
Sensor values:
Activate the sensor values that should be sent to the
heat pump for supply temperature calculations, select
from a list.
suPPly Water Control ler
Default: Inactive
Setting range: Active, Inactive
Activate if a supply water controller is connected to the
Base PRO system.
See separate documentation for more information.
KnX g ateWay
Default: Inactive
Setting range: Active, Inactive
Activate if a KNX gateway is connected to the Base PRO
system.
See separate documentation for more information.
14.11 Trends
This menu shows temperature and utilisation trends for
the last 7 days, for up to 12 rooms at the time.
Select between showing:
Curves showing average system temperature,
average system setpoint temperature and outdoor
temperature (if an outdoor sensor is installed).
Curves showing indoor temperature and setpoint
temperature for a room as well as outdoor
temperature (if an outdoor sensor is installed).
Bars showing a utilisation factor per room. The
factor is the percentage of time when the actuator
has been opened.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
106
UPONOR SMATRIX BASE/BASE PRO · INSTALLATION AND OPERATION MANUAL

Table of Contents

Other manuals for Uponor Smatrix Base

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uponor Smatrix Base and is the answer not in the manual?

Uponor Smatrix Base Specifications

General IconGeneral
BrandUponor
ModelSmatrix Base
CategoryHeating System
LanguageEnglish

Related product manuals