Vertiv | SmartAisle2 | User Manual 113
Operation & Display Panel
Chapter 3: Operation & Display Panel
In this chapter, the SmartAisle2 product including power before checking, power, system debugging and shutdown
will be explained in detail.
3.1. Checks prior to Start
The following checklist needs to be screened through to confirm if all the following items and parameters are
met:
Table 3-1 Checklist prior to Start
Types of
parameters
Checklist items
Test
result
Mechanical
All cables, circuit connectors tightened, no loosening of the fastening screw
And base building has been a reliable connection
Fasteners for transportation have been removed
After installation is complete, or debris inside the device have been removed around (e.g.,
shipping materials, construction materials, tools, etc.)
Cooling
Follow the instructions on the label at the valve, opening all the valves in the refrigerant circuit
The cooling pipe system has been qualified pressure leak test and confirm
The humidification system for drainage pipe system and is firmly connected to the material in
accordance with claim leak
Ensure proper refrigerant charge
Compressor plus tropical warm-up has been more than 12 hours
If located above the room temperature and 18 °C has a certain heat load. If not provided, preferably
by using other heating means or manual operation of the unit itself and force the adjacent heater
equipment (sure to follow the method of operation “Liebert CRV + Series User Manual precision
air conditioning air”), while preheating to the room environment, to ensure heat load necessary
debugging
Confirmation level switch cable is connected and the float rod may work level
Outdoor air-cooled condenser power isolation switch has been closed
Supply and
distribution
Measured with a multi-meter voltage feed line is normal, and the same equipment nameplate
rated voltage
The system does not open electrical circuit, short circuit
Verify that all electrical wiring or control properly tighten all electrical control connectors
Each sub-closing operation switch, each switch test the mechanical properties of normal
Industrial rack PDU male female connector installed properly
Illumination Lighting controller power is properly connected
Electric door
Line resistance and no bump manual door
Cable lashing rails in the firm, cannot be involved in the drive gears, belts
Remove metallic debris from the rail