Vertiv | SmartAisle2 | User Manual 128
General Maintenance
4.4. Breakdown and Disposal
SmartAisle2 contains substances that are harmful to the environment and the components. At the end of product
or service life, the disposal must be done by trained professionals. It must be sent to the authorized center as per
the local protocols and laws of the country or region.
4.5. Troubleshooting
Q1: Roof don’t close.
Ans: First ensure electromagnetic lock armature can move by loosening screw a little bit; second ensure lock
connector pin is inserted in house correctly.
Q2: Roof don’t open
Ans: Firstly remove roof rotable plate fix screw used for transportation; secondly check whether the rotable plate
impacts the roof frame.
Q3: Light don’t work, color is wrong
Ans: First ensure light connector pin is inserted in house correctly; second check wire connector sequence.
Q4: HMI display “out of range”, display is abnormal
Ans: First ensure video source resolution is 1024*768; second use auto adjusting by HMI OSD.
Q5: Electrical door don’t move, moves too slow, have friction noise
Ans: Remove chipping in rail, adjust glass hang to have gap between glass and metal column and F guide.
Q6: Electrical door remain open don’t close
Ans: Ensure left door belt fixture fixed on top belt, right door belt fixture fixed on bottom belt, nothing blocks safe
beam sensor.
• General Troubleshooting for various components can be found in their respective user manuals, meaning
air conditioning troubleshooting is available with the CRV+ series PAC manuals.