JOHNSON CONTROLS
184
SECTION 9 - MAINTENANCE
Form 201.47-ICOM1
Issue date: 17/11/2022
Chilled liquid and suction temperature sensor input voltage
Table 36 - Temperature input voltage sensor (Measured signal to shield at the sensor)
Temperature ºF
(°c)
Voltage
Temperature °F
(°c)
Voltage
Temperature °F
(°c)
Voltage
16.1 (-8.8) 1.52 35.9 (2.2) 2.19 55.6 (13.1) 2.85
16.7 (-8.5) 1.54 36.5 (2.5) 2.21 56.3 (13.5) 2.87
17.3 (-8.2) 1.56 37.0 (2.8) 2.23 56.9 (13.8) 2.89
17.9 (-7.8) 1.58 37.6 (3.1) 2.25 57.5 (14.2) 2.91
18.5 (-7.5) 1.60 38.2 (3.4) 2.27 58.1 (14.5) 2.93
19.1 (-7.2) 1.62 38.7 (3.7) 2.29 58.7 (14.8) 2.95
19.7 (-6.8) 1.64 39.3 (4.1) 2.30 59.4 (15.2) 2.97
20.3 (-6.5) 1.66 39.9 (4.4) 2.32 60.0 (15.6) 2.99
20.9 (-6.2) 1.68 40.4 (4.7) 2.34 60.6 (15.9) 3.01
21.5 (-5.8) 1.70 41.0 (5.0) 2.36 61.3 (16.3) 3.03
22.1 (-5.5) 1.72 41.6 (5.3) 2.38 61.9 (16.6) 3.05
22.7 (-5.2) 1.74 42.1 (5.6) 2.40 62.5 (16.9) 3.07
23.3 (-4.8) 1.76 42.7 (5.9) 2.42 63.2 (17.3) 3.09
23.9 (-4.5) 1.78 43.3 (6.3) 2.44 63.8 (17.7) 3.11
24.5 (-4.2) 1.80 43.9 (6.6) 2.46 64.5 (18.1) 3.13
25.0 (-3.9) 1.82 44.4 (6.9) 2.48 65.1 (18.4) 3.14
25.6 (-3.6) 1.84 45.0 (7.2) 2.50 65.8 (18.8) 3.16
26.2 (-3.2) 1.86 45.6 (7.5) 2.52 66.5 (19.2) 3.18
26.8 (-2.9) 1.88 46.2 (7.9) 2.54 67.1 (19.5) 3.20
27.3 (-2.6) 1.90 46.7 (8.2) 2.56 67.8 (19.9) 3.22
27.9 (-2.8) 1.91 47.3 (8.5) 2.58 68.5 (20.3) 3.24
28.5 (-1.9) 1.93 47.9 (8.8) 2.60 69.2 (20.7) 3.26
29.0 (-1.7) 1.95 48.5 (9.2) 2.62 69.9 (21.1) 3.28
29.6 (-1.3) 1.97 49.1 (9.5) 2.64 70.6 (21.4) 3.30
30.2 (-1) 1.99 49.7 (9.8) 2.66 71.3 (21.8) 3.32
30.8 (-0.7) 2.01 50.3 (10.2) 2.68 72.0 (22.2) 3.34
31.3 (-0.4) 2.03 50.8 (10.4) 2.70 72.7 (22.6) 3.36
31.9 (-0.1) 2.05 51.4 (10.8) 2.71 73.4 (23) 3.38
32.5 (0.3) 2.07 52.0 (11.1) 2.73 74.2 (23.4) 3.40
33.0 (0.6) 2.09 52.6 (11.4) 2.75 74.9 (23.8) 3.42
33.6 (0.9 ) 2.11 53.2 (11.8) 2.77
34.2 (1.2) 2.13 53.8 (12.1) 2.79
34.8 (1.5) 2.15 54.5 (12.5) 2.81
35.3 (1.8) 2.17 55.0 (12.8) 2.83