EasyManuals Logo

York YVAA User Manual

York YVAA
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #98 background imageLoading...
Page #98 background image
JOHNSON CONTROLS
98
SECTION 6 - COMMISSIONING
Form 201.47-ICOM1
Issue date: 17/11/2022
A. 
the lowest possible ambient temperature must be

......-or-
B.         
completing the following steps:
Remove the power to the water box heaters

Drain the evaporator
Leave the evaporator drain valves open

used but continuous power to the chiller control panel,

be guaranteed during periods of subfreezing ambient
temperatures, then one of the freeze damage protec-
tion protocols in the following table must be followed:
Table 16 - YVAA freeze damage protection requirements
Chiller control of chilled fluid
circuit pumps
Actuated suction service
isolation valve
Water box immersion heaters
Ambient air temperatures from
32⁰F (0⁰C) down to 0⁰F (-17.8⁰C)
Required if actuated suction
service isolation valve is not
selected
Required if chilled fluid pumps are
not controlled by chiller control
panel
Not required
Ambient air temperatures below
0⁰F (-17.8⁰C) down to -20⁰F
(-28⁰C)
Required Required Required

Table of Contents

Other manuals for York YVAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YVAA and is the answer not in the manual?

York YVAA Specifications

General IconGeneral
RefrigerantR-134a
CondenserWater-cooled
Compressor TypeScrew
EfficiencyHigh
Operating Voltage380V/3/60Hz
WeightVaries with model; consult factory
DimensionsVaries with model; consult factory

Related product manuals