Program features 133
Programmable analog output
One programmable current output (0…20 mA) is available. Analog output signal can
be inverted, filtered and the maximum and minimum values can be adjusted. The
analog output signals can be proportional to motor speed, output frequency, output
current, motor torque, motor power, etc. The update cycle for the analog output is
2ms.
Analog output can be controlled with Sequence programming. It is also possible to
write a value to an analog output through a serial communication link.
Settings
Diagnostics
Parameter Additional information
Group 15 ANALOG OUTPUTS AO value selection and processing
Group 35 MOTOR TEMP MEAS AO in motor temperature measurement
8423/8433/…/8493 AO control with Sequence programming
Actual signal Additional information
0124 AO value
0170 AO control values defined by Sequence programming
Fault
PAR AO SCALE Incorrect AO signal scaling (1503 < 1502)