Fault tracing 351
Alarm messages generated by the drive
CODE ALARM CAUSE WHAT TO DO
2001 OVERCURRENT
0308 bit 0
(programmable fault
function 1610)
Output current limit
controller is active.
High ambient
temperature.
Check ambient conditions. Load
capacity decreases if installation site
ambient temperature exceeds 40 °C
(104 °F). See section Derating on
page 376.
For more information, see fault 0001
in Fault messages generated by the
drive on page 357.
2002 OVERVOLTAGE
0308 bit 1
(programmable fault
function 1610)
DC overvoltage
controller is active.
For more information, see fault 0002
in Fault messages generated by the
drive on page 357.
2003 UNDERVOLTAGE
0308 bit 2
DC undervoltage
controller is active.
For more information, see fault 0003
in Fault messages generated by the
drive on page 351.
2004 DIR LOCK
0308 bit 3
Change of direction is
not allowed.
Check parameter 1003 DIRECTION
settings.
2005 IO COMM
0308 bit 4
(programmable fault
function 3018, 3019)
Fieldbus
communication break
Check status of fieldbus
communication. See chapter Fieldbus
control with embedded fieldbus on
page 313, chapter Fieldbus control
with fieldbus adapter on page 339 or
appropriate fieldbus adapter manual.
Check fault function parameter
settings.
Check connections.
Check if master can communicate.
2006 AI1 LOSS
0308
bit 5
(programmable fault
function 3001, 3021)
Analog input AI1 signal
has fallen below limit
defined by parameter
3021 AI1 FAULT
LIMIT.
For more information, see fault 0007
in Fault messages generated by the
drive on page 357.
2007 AI2 LOSS
0308 bit 6
(programmable fault
function 3001, 3022)
Analog input AI2 signal
has fallen below limit
defined by parameter
3022 AI2 FAULT
LIMIT.
For more information, see fault in
0008 Fault messages generated by
the drive on page 357.
2008 PANEL LOSS
0308 bit 7
(programmable fault
function 3002)
Control panel selected
as active control
location for drive has
ceased
communicating.
For more information, see fault 0010
in Fault messages generated by the
drive on page 357.
2009 DEVICE
OVERTEMP
0308 bit 8
Drive IGBT
temperature is
excessive. Alarm limit
depends on the drive
type and size.
Check ambient conditions. See also
section Derating on page 376.
Check air flow and fan operation.
Check motor power against drive
power.

Table of Contents

Other manuals for ABB ACS355 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 series and is the answer not in the manual?

ABB ACS355 series Specifications

General IconGeneral
BrandABB
ModelACS355 series
CategoryController
LanguageEnglish

Related product manuals