Actual signals and parameters 259
32 SUPERVISION Signal supervision. Supervision status can be monitored
with relay or transistor output. See parameter groups 14
RELAY OUTPUTS and 18 FREQ IN & TRAN OUT.
3201 SUPERV 1
PARAM
Selects the first supervised signal. Supervision limits are
defined by parameters 3202 SUPERV 1 LIM LO and 3203
SUPERV 1 LIM HI.
Example 1: If 3202 SUPERV 1 LIM LO <
3203 SUPERV 1
LIM HI
Case A = 1401 RELAY OUTPUT 1 value is set to SUPRV1
OVER. Relay energizes when value of the signal selected
with 3201 SUPERV 1 PARAM exceeds the supervision limit
defined by 3203 SUPERV 1 LIM HI. The relay remains
active until the supervised value drops below the low limit
defined by 3202 SUPERV 1 LIM LO.
Case B = 1401 RELAY OUTPUT 1 value is set to SUPRV1
UNDER. Relay energizes when value of the signal selected
with 3201 SUPERV 1 PARAM drops below the supervision
limit defined by 3202 SUPERV 1 LIM LO. The relay remains
active until the supervised value rises above the high limit
defined by 3203 SUPERV 1 LIM HI.
103
All parameters
No. Name/Value Description Def/FbEq
t
t
t
HI par. 3203
Value of supervised parameter
LO par. 3202
Energized (1)
Energized (1)
0
0
Case A
Case B

Table of Contents

Other manuals for ABB ACS355 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 series and is the answer not in the manual?

ABB ACS355 series Specifications

General IconGeneral
BrandABB
ModelACS355 series
CategoryController
LanguageEnglish

Related product manuals