Appendix: Safe torque off (STO) 421
Activation switch
In the wiring diagram above (page 419), the activation switch has the designation (K).
This represents a component such as a manually operated switch, an emergency
stop push button switch, or the contacts of a safety relay or safety PLC.
If a manually operated activation switch is used, the switch must be of a type that
can be locked out to the open position.
Inputs IN1 and IN2 must open/close within 200 ms of each other.
Cable types and lengths
Double-shielded twisted-pair cable is recommended.
Maximum cable length 300 m (984 ft) between activation switch (K) and drive
control unit.
Note: A short-circuit in the wiring between the switch and an STO terminal causes a
dangerous fault and therefore it is recommended to use a safety relay (including
wiring diagnostics), or a wiring method (shield grounding, channel separation) which
reduces or eliminates the risk caused by the short-circuit.
Note: The voltage at the INx terminals of each drive must be at least 13 V DC to be
interpreted as “1”.
Grounding of protective shields
Ground the shield in the cabling between the activation switch and the control
board at the control board.
Ground the shield in the cabling between two control boards at one control board
only.

Table of Contents

Other manuals for ABB ACS355 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 series and is the answer not in the manual?

ABB ACS355 series Specifications

General IconGeneral
BrandABB
ModelACS355 series
CategoryController
LanguageEnglish

Related product manuals