Actual signals and parameters 289
5132 FBA CPI FW
REV
Displays the common program revision of the adapter
module in format axyz, where:
• a = major revision number
• xy = minor revision numbers
• z = correction letter.
Example: 190A = revision 1.90A
Common program revision of the adapter module 1 = 1
5133 FBA APPL FW
REV
Displays the application program revision of the adapter
module in format axyz, where:
• a = major revision number
• xy = minor revision numbers
• z = correction letter.
Example: 190A = revision 1.90A
Application program revision of the adapter module 1 = 1
52 PANEL COMM Communication settings for the control panel port on the
drive
5201 STATION ID Defines the address of the drive. Two units with the same
address are not allowed on-line.
1
1…247 Address 1 = 1
5202 BAUD RATE Defines the transfer rate of the link. 9.6 kb/s
1.2 kb/s 1.2 kbit/s 1 =
0.1 kbit/s
2.4 kb/s 2.4 kbit/s
4.8 kb/s 4.8 kbit/s
9.6 kb/s 9.6 kbit/s
19.2 kb/s 19.2 kbit/s
38.4 kb/s 38.4 kbit/s
57.6 kb/s 57.6 kbit/s
115.2 kb/s 115.2 kbit/s
5203 PARITY Defines the use of parity and stop bit(s). The same setting
must be used in all on-line stations.
8 NONE 1
8 NONE 1 8 data bits, no parity bit, one stop bit 0
8 NONE 2 8 data bits, no parity bit, two stop bits 1
8 EVEN 1 8 data bits, even parity indication bit, one stop bit 2
8 ODD 1 8 data bits, odd parity indication bit, one stop bit 3
5204 OK
MESSAGES
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
0
0…65535 Number of messages 1 = 1
All parameters
No. Name/Value Description Def/FbEq