288 Actual signals and parameters
RS-485 FSCA-01 RS-485 adapter module 485
5102 FB PAR 2 These parameters are adapter module-specific. For more
information, see the module manual. Note that not all of
these parameters are necessarily visible.
……
5126 FB PAR 26
5127 FBA PAR
REFRESH
Validates any changed adapter module configuration
parameter settings. After refreshing, the value reverts
automatically to DONE.
DONE Refreshing done 0
REFRESH Refreshing 1
5128 FILE CPI FW
REV
Displays the parameter table revision of the fieldbus adapter
module mapping file stored in the memory of the drive.
Format is xyz where:
• x = major revision number
• y = minor revision number
• x = correction letter.
0000…FFFF
hex
Parameter table revision 1 = 1
5129 FILE CONFIG
ID
Displays the drive type code of the fieldbus adapter module
mapping file stored in the memory of the drive.
0000…FFFF
hex
Drive type code of fieldbus adapter module mapping file 1 = 1
5130 FILE CONFIG
REV
Displays the fieldbus adapter module mapping file revision
stored in the memory of the drive in decimal format.
Example: 1 = revision 1.
0000…FFFF
hex
Mapping file revision 1 = 1
5131 FBA STATUS Displays the status of the fieldbus adapter module
communication.
IDLE Adapter is not configured. 0
EXECUT INIT Adapter is initializing. 1
TIME OUT A time-out has occurred in the communication between the
adapter and the drive.
2
CONFIG
ERROR
Adapter configuration error: The major or minor revision
code of the common program revision in the fieldbus
adapter module is not the revision required by the module
(see parameter 5132 FBA CPI FW REV) or mapping file
upload has failed more than three times.
3
OFF-LINE Adapter is off-line. 4
ON-LINE Adapter is on-line. 5
RESET Adapter is performing a hardware reset. 6
All parameters
No. Name/Value Description Def/FbEq