392 Technical data
Category C1
The emission limits are complied with the following provisions:
1. The optional EMC filter is selected according to the ABB documentation and
installed as specified in the EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. For the maximum motor cable length with 4 kHz switching frequency, see page
386.
WARNING! In a domestic environment, this product may cause radio inference, in
which case supplementary mitigation measures may be required.
Category C2
The emission limits are complied with the following provisions:
1. The optional EMC filter is selected according to the ABB documentation and
installed as specified in the EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. For the maximum motor cable length with 4 kHz switching frequency, see page
386.
WARNING! In a domestic environment, this product may cause radio inference, in
which case supplementary mitigation measures may be required.
Category C3
The immunity performance of the drive complies with the demands of
IEC/EN 61800-3, second environment (see page 391 for IEC/EN 61800-3
definitions).
The emission limits are complied with the following provisions:
1. The internal EMC filter is connected (the metal screw at EMC is in place) or the
optional EMC filter is installed.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. With the internal EMC filter: motor cable length 30 m (100 ft) with 4 kHz switching
frequency. For the maximum motor cable length with an optional external EMC
filter, see page 386.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is expected
if the drive is used on such a network.

Table of Contents

Other manuals for ABB ACS355 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 series and is the answer not in the manual?

ABB ACS355 series Specifications

General IconGeneral
BrandABB
ModelACS355 series
CategoryController
LanguageEnglish

Related product manuals