Start-up, control with I/O and ID run 63
Performing a manual start-up
For the manual start-up, you can use the basic control panel or the assistant control
panel. The instructions below are valid for both control panels, but the displays shown
are the basic control panel displays, unless the instruction applies to the assistant
control panel only.
Before you start, ensure that you have the motor nameplate data on hand.
POWER-UP
Apply input power.
The basic control panel powers up into the
Output mode.
The assistant control panel asks if you want to
run the Start-up assistant. If you press , the
Start-up assistant is not run, and you can
continue with manual start-up in a similar manner
as described below for the basic control panel.
MANUAL ENTRY OF START-UP DATA (parameter group 99)
If you have an assistant control panel, select the
language (the basic control panel does not
support languages). See parameter 9901 for the
values of the available language alternatives.
For instructions on how to set parameters with the
assistant control panel, see section Assistant control
panel on page 86.
Select the motor type (9903).
•1(AM): Asynchronous motor
•2(PMSM): Permanent magnet synchronous
motor.
Setting of parameter 9903 is shown below as an
example of parameter setting with the basic control
panel. You find more detailed instructions in section
Basic control panel on page 76.
1. To go to the Main menu, press if the bottom
line shows OUTPUT; otherwise press
repeatedly until you see MENU at the bottom.
2. Press keys / until you see “PAr”, and
press .
3. Find the appropriate parameter group with keys
/ and press .
Do you want to
use the start-up
assistant?
Yes
No
EXIT OK
00:00
REM
CHOICE
9901 LANGUAGE
CANCEL SAVE
00:00
PAR EDIT
[0]
ENGLISH
REM