Fault tracing 367
Embedded fieldbus faults
Embedded fieldbus faults can be traced by monitoring group 53 EFB PROTOCOL
parameters. See also fault/alarm SERIAL 1 ERR (0028).
No master device
If there is no master device on line, parameter 5306 EFB OK MESSAGES and 5307
EFB CRC ERRORS values remain unchanged.
What to do:
Check that the network master is connected and properly configured.
Check the cable connection.
Same device address
If two or more devices have the same address, parameter 5307 EFB CRC ERRORS
value increases with every read/write command.
What to do:
Check the device addresses. No two devices on line may have the same address.
Incorrect wiring
If the communication wires are swapped (terminal A on one device is connected to
terminal B on another device), parameter 5306 EFB OK MESSAGESS value remains
unchanged and parameter 5307 EFB CRC ERRORS increases.
What to do:
Check the RS-232/EIA-485 interface connection.