164 Program features
It is also possible to activate jogging function 1 or 2 through fieldbus. Jogging
function 1 uses constant speed 7 and jogging function 2 uses constant speed 6. Both
functions use acceleration/deceleration ramp pair 2.
Settings
Diagnostics
Parameter Additional information
1010 Jogging activation
1208 Jogging speed
1208/1207 Jogging speed for jogging function 1/2 activated through
fieldbus
2112 Zero speed delay
2205, 2206 Acceleration and deceleration times
2207 Acceleration and deceleration ramp shape time: Set to
zero during the jogging (ie, linear ramp).
Actual signal Additional information
0302 Jogging 1/2 activation through fieldbus
1401 Jogging function status through RO 1
1402/1403/1410 Jogging function status through RO 2…4. With option
MREL-01 only.
1805 Jogging function status through DO

Table of Contents

Other manuals for ABB ACS355 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 series and is the answer not in the manual?

ABB ACS355 series Specifications

General IconGeneral
Power Range0.37 to 22 kW
Protection ClassIP20
Output Frequency0 to 500 Hz
Braking ChopperBuilt-in
Control MethodScalar control, Vector control
Ambient Temperature-10 to +50 °C
Communication ProtocolsModbus, CANopen
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature
Cooling MethodAir-cooled
Number of Phases3-phase

Related product manuals