182 Actual signals and parameters
Differences between the default values in E and U type
drives
The type designation label shows the type of the drive, see section Type designation
key on page 31.
The following table lists the differences between the parameter default values in the E
and U type drives.
No. Name E type
EMC filter screw
connected
U type
EMC filter screw
disconnected
9905 MOTOR NOM VOLT 230/400V 230/460V
9907 MOTOR NOM FREQ 50 60
9909 MOTOR NOM POWER [kW] [hp]
1105 REF1 MAX 50 60
1202 CONST SPEED 1 56
1203 CONST SPEED 2 10 12
1204 CONST SPEED 3 15 18
1205 CONST SPEED 4 20 24
1206 CONST SPEED 5 25 30
1207 CONST SPEED 6 40 48
1208 CONST SPEED 7 50 60
2002 MAXIMUM SPEED 1500 1800
2008 MAXIMUM FREQ 50 60