Actual signals and parameters 291
8 EVEN 1 Even parity indication bit, one stop bit, 8 data bits 2
8 ODD 1 Odd parity indication bit, one stop bit, 8 data bits 3
5305 EFB CTRL
PROFILE
Selects the communication profile. See section
Communication profiles on page 328.
ABB DRV
LIM
ABB DRV LIM ABB drives limited profile 0
DCU PROFILE DCU profile 1
ABB DRV
FULL
ABB drives profile 2
5306 EFB OK
MESSAGES
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
0
0…65535 Number of messages 1 = 1
5307 EFB CRC
ERRORS
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note: High electromagnetic noise levels generate errors.
0
0…65535 Number of messages 1 = 1
5310 EFB PAR 10 Selects an actual value to be mapped to Modbus register
40005.
103
0…65535 Parameter index 1 = 1
5311 EFB PAR 11 Selects an actual value to be mapped to Modbus register
40006.
104
0…65535 Parameter index 1 = 1
5312 EFB PAR 12 Selects an actual value to be mapped to Modbus register
40007.
0
0…65535 Parameter index 1 = 1
5313 EFB PAR 13 Selects an actual value to be mapped to Modbus register
40008.
0
0…65535 Parameter index 1 = 1
5314 EFB PAR 14 Selects an actual value to be mapped to Modbus register
40009.
0
0…65535 Parameter index 1 = 1
5315 EFB PAR 15 Selects an actual value to be mapped to Modbus register
40010.
0
0…65535 Parameter index 1 = 1
5316 EFB PAR 16 Selects an actual value to be mapped to Modbus register
40011.
0
0…65535 Parameter index 1 = 1
5317 EFB PAR 17 Selects an actual value to be mapped to Modbus register
40012.
0
0…65535 Parameter index 1 = 1
All parameters