292 Actual signals and parameters
5318 EFB PAR 18 For Modbus: Sets an additional delay before the drive
begins transmitting response to the master request.
0
0…65535 Delay in milliseconds 1 = 1
5319 EFB PAR 19 ABB drives profile (ABB DRV LIM or ABB DRV FULL)
Control word.
0000 hex
0000…FFFF
hex
Control word
5320 EFB PAR 20 ABB drives profile (ABB DRV LIM or ABB DRV FULL)
Status word.
0000 hex
0000…FFFF
hex
Status word
54 FBA DATA IN Data from the drive to the fieldbus controller through a
fieldbus adapter. See chapter Fieldbus control with fieldbus
adapter on page 339.
Note: In adapter module the parameter group number is 3.
5401 FBA DATA IN 1 Selects data to be transferred from the drive to the fieldbus
controller.
0Not in use
1…6 Control and status data words
101…9999 Parameter index
5402 FBA DATA IN 2 See 5401 FBA DATA IN 1.
……
5410 FBA DATA IN
10
See 5401 FBA DATA IN 1.
All parameters
No. Name/Value Description Def/FbEq
5401 setting Data word
1Control word
2REF1
3REF2
4 Status word
5Actual value 1
6Actual value 2

Table of Contents

Other manuals for ABB ACS355 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 series and is the answer not in the manual?

ABB ACS355 series Specifications

General IconGeneral
Power Range0.37 to 22 kW
Protection ClassIP20
Output Frequency0 to 500 Hz
Braking ChopperBuilt-in
Control MethodScalar control, Vector control
Ambient Temperature-10 to +50 °C
Communication ProtocolsModbus, CANopen
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature
Cooling MethodAir-cooled
Number of Phases3-phase