258 Actual signals and parameters
3104 AR
OVERCURRE
NT
Activates/deactivates the automatic reset for the
overcurrent fault. Automatically resets fault
OVERCURRENT (0001) after the delay set by parameter
3103 DELAY TIME.
DISABLE
DISABLE Inactive 0
ENABLE Active 1
3105 AR
OVERVOLTAG
E
Activates/deactivates the automatic reset for the
intermediate link overvoltage fault. Automatically resets fault
DC OVERVOLT (0002) after the delay set by parameter
3103 DELAY TIME.
DISABLE
DISABLE Inactive 0
ENABLE Active 1
3106 AR
UNDERVOLTA
GE
Activates/deactivates the automatic reset for the
intermediate link undervoltage fault. Automatically resets
fault DC UNDERVOLT (0006) after the delay set by
parameter 3103 DELAY TIME.
DISABLE
DISABLE Inactive 0
ENABLE Active 1
3107 AR AI<MIN Activates/deactivates the automatic reset for AI<MIN
(analog input signal under the allowed minimum level) faults
AI1 LOSS (0007) and AI2 LOSS (0008). Automatically
resets the fault after the delay set by parameter 3103
DELAY TIME.
DISABLE
DISABLE Inactive 0
ENABLE Active
WARNING! The drive may restart even after a long
stop if the analog input signal is restored. Ensure that
the use of this feature will not cause danger.
1
3108 AR EXTERNAL
FLT
Activates/deactivates the automatic reset for faults EXT
FAULT 1 (0014) and EXT FAULT 2 (0015). Automatically
resets the fault after the delay set by parameter 3103
DELAY TIME.
DISABLE
DISABLE Inactive 0
ENABLE Active 1
All parameters
No. Name/Value Description Def/FbEq