18 Introduction to the manual
Compatible products
Check the compatibility of the earlier versions with your local ABB representative.
See also section FSO module version handling on page 37.
ACS880 drives and option modules
• ACS880 series without “No FSO support” sticker
• ACS880 primary control program: version 2.21 or later
• FSE-31 pulse encoder interface module: revision D or later
• FENA-21 Ethernet adapter module: version 3.05 or later
• FPNO-21 PROFINET fieldbus adapter module: version 1.00 or later
Application control programs
FSO-21 behavior is independent from application control program, thus all application
control programs are supported by FSO-21. Example applications:
• Machinery control program v2.40 or later
• Crane control program v2.1 or later
• Tower crane control program v1.0 or later
• Winch control program v1.0 or later
• Winder control program v1.10 or later
• PCP/ESP control program (+N5200) v1.1 or later
• PCP/ESP control program SynRM v1.1.1.0 or later
• Spinning control program v1.0 or later
• Rod pump control program v1.0 or later
Note: If you want to use the possibility to switch the motor speed feedback between
encoder and estimate, ACS880 primary control program version 2.51 (or later) and
FSE-31 revision F (or later) are required. See section Motor speed feedback on page
44.
DCS880 drives and option modules
• DCS880 drive modules
• DCS880 firmware, version 2.07 or later
• FSE-31 pulse encoder interface module: revision D or later
• FENA-21 Ethernet adapter module: version 3.11 or later
• FPNO-21 PROFINET fieldbus adapter module: version 1.00 or later
Note that there are fundamental differences how a DCS880 drive operates when
compared to an ACS880 drive. This leads to the following limitations:
• STO takes 500 ms to be achieved in DCS880 drives. Further, a secondary
switching device (i.e. AC-breaker, medium voltage breaker or DC-breaker) must