This chapter describes the password usage, outlines the configuration process and
gives examples of how to configure the FSO module to implement each safety
function as described in chapter Safety functions.
Competence
The person who configures the safety functions in the FSO module must be a
competent person as required by IEC 61508-1 clause 6. In this context, the person
must have adequate expertise and knowledge of functional safety, the safety
functions as well as the configuration of the FSO module. ABB has training courses
available on the FSO module.
Password
You need a password to be able to upload the parameters from the FSO and
download the modified parameters from your PC to the FSO and the drive.
The password is set to “12345678” at the factory. The password must contain 4…8
digits. When you change it, do not forget the new password; otherwise you have to do
a factory reset to the FSO which clears the configuration and resets the parameters
to the factory defaults. The password is reset to the default “12345678”.