PROFIsafe 283
6. To check the Device number of the FENA module, select the General tab.
Diagnostic messages related to F-Parameters
The diagnostics messages in this table are caused by problems in the
F-Parameter processing that takes place only when the controller station sends the
F-Parameters to FB module. This happens normally only when the controller station
starts up the PROFINET communication with the FB module.
Value
(hex)
Description Notes
64
(0x0040)
Mismatch of safety destination
address (F_Dest_Add).
F_Dest_Add did not match the value
configured in the safety parameters
(PROFIsafe.11 PROFIsafe F_Dest_Add).
65
(0x0041)
Safety destination address is not valid
(F_Dest_Add).
F_Dest_Add of 0 or FFFFh is not allowed.
A valid F_Dest_Add is within range
1...65534.
66
(0x0042)
Safety source address is not valid
(F_Source_Add).
F_Source_Add of 0 or FFFFh is not
allowed.
A valid F_Source_Add is within range
1...65534.
67
(0x0043)
Safety watchdog time value is 0 ms
(F_WD_Time).
Watchdog time 0 ms is not allowed.
A valid F_WD_Time is within range
1...65535.