Rockwell Automation Publication 2711P-UM007D-EN-P - December 2015 35
Install the PanelView Plus 7 Standard Terminal Chapter 2
Connect Power
The terminals have a 24-V DC non-isolated power supply at these power
ratings:
• 24V DC nominal (18…30V DC)
• 35 W maximum (1.46A at 24V DC)
The terminals support operation from a safety extra low voltage (SELV) or
protective extra-low voltage (PELV) 24V DC power supply. Supported power
supplies include catalog numbers 1606-XLP95E, 1606-XLP100E, and
2711P-RSACDIN.
To power the terminal from the same power source as other equipment, use a
DC power bus.
To connect the operator terminal to a DC power source, follow these steps.
1. Verify that the wiring is not connected to a power source.
2. Strip 7 mm (0.28 in.) of insulation from your power supply wires.
3. Secure the DC power wires to the marked terminals (+ and –) on the
terminal block.
4. Secure the earth ground wire to the GND terminal on the terminal
block.
The GND terminal must be connected to a low-impedance earth
ground.
ATTENTION: The power supply is internally protected against reverse
polarity. Connecting DC+ or DC- to the earth ground terminal can damage
the terminal. Connecting AC power, or more than 30V DC, can also damage
the terminal.
ATTENTION: Use a SELV or PELV supply as required by local wiring codes for
your installation. The SELV and PELV power sources provide protection so
that under normal and single fault conditions, the voltage between
conductors and earth ground does not exceed a safe value.
6
66
GNDDC+ DC–
Series B terminal with dual
Ethernet ports shown.