68 Rockwell Automation Publication 2711P-UM007D-EN-P - December 2015
Chapter 3 Configure Terminal Settings
Check Integrity of
Application Files
It is good practice to check the integrity of the .mer application that is loaded
in the terminal and the runtime files. Errors, warnings, and information
messages are logged to a file. You can view the log and clear items from the log.
1. Press Terminal Settings, then choose File Integrity Check.
2. Press either of the Enable options to disable integrity checks of the .mer
application or the runtime files.
Integrity checks are automatically performed on the application .mer file
and runtime files. If you disable either of these functions, the files are not
checked and the log file is not updated.
3. Press OK to save changes.
Follow these steps to view the log generated by runtime files.
1. Press View Log from the File Integrity Check dialog box.
2. To display details for that event, select an event and press More Details.
3. To clear all details from the log, press Clear All.
4. To return to previous dialog box, press Close.
TIP Runtime files enable applications to run on the terminal. If the terminal is
not functioning correctly, a review of the logs can identify an error in a
runtime file.