When the box is fixed on the wall proceed for main power cabling:
The power of the panel must be separate, and must be taken from the main power panel of the place.
The power line must be protected by devices of sectioning and protection in accordance with local regulations.
Must be connect after 16A circuit breaker device with operating curve type C, with supply conductors, (including earth), minimum
section of 1.5 mm2.
Wiring connection in the panel box must be like in figure below:
- Connect phase, neutral and earth to the fuse housing like in figure
- make sure that the earth connection is like the fig in next page
IMPORTANT: Pay max attention during the cabling
IMPORTANT: to avoid electric shock, wiring system without power
WIRING MAIN POWER AND EARTH