Category Error Code Description How to fix them
H’11010122
The input priority in the EDS
file is mismatched.
1. Check if the product information and the EDS file
match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
H’11010123
The output connection type
parameters in the EDS file
are mismatched.
1. Check if the product information and the EDS file
match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
H’11010124
The input connection type
parameters in the EDS file
are mismatched.
1. Check if the product information and the EDS file
match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
H’11010125
The redundant ownership
output parameters in the
EDS file are mismatched.
1. Check if the product information and the EDS file
match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
H’11010126
The configuration size
parameters in the EDS file
are mismatched.
1. Check if the product information and the EDS file
match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
H’11010129
The configuration path
parameters in the EDS file
are mismatched.
1. Check if the product information and the EDS file
match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
H’11010132
The EDS file does not
support Null forward open.
1. Check if the product information and the EDS file
match.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
Data
Exchange
Setup Error
H’12010100 I/O connections duplicated
1. Check if the system has created the I/O
connections.
2. Change the connection type to Listen Only.
H’12010106
Scanner ownership of I/O
connections conflicts
1. Check the scanner owner.
2. Reconfigure the invalid scanner.
3. Change the connection to multicast.
H’12010110
Incorrect adapter
configuration
1. Check the I/O connection status.
2. Activate the I/O connections again.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS132P-A and is the answer not in the manual?

Delta AS132P-A Specifications

General IconGeneral
BrandDelta
ModelAS132P-A
CategoryNetwork Hardware
LanguageEnglish

Related product manuals