4-50 PQM Power Quality Meter GE Power Management
4.5 S4 ALARMS/CONTROL 4 PROGRAMMING
4
4.5.7 PULSE INPUT
Figure 4–31: SETPOINTS PAGE 4 – ALARMS/CONTROL / PULSE INPUT
]] SETPOINTS
]] S4 ALARMS/CONTROL
] PULSE INPUT
]
PULSE INPUT 1
RELAY: OFF
PULSE INPUT 1
LEVEL
≥
≥≥
≥
100 Units
PULSE INPUT 1
DELAY: 10.0 s
]] SETPOINTS
]] S5 TESTING
SETPOINT
Range: ALARM, AUX1, AUX2, AUX3, OFF
PULSE INPUT 2
RELAY: OFF
PULSE INPUT 2
LEVEL
≥
≥≥
≥
100 Units
PULSE INPUT 2
DELAY: 10.0 s
Range: 1 to 65000, Step 1
PULSE INPUT 3
RELAY: OFF
PULSE INPUT 3
LEVEL
≥
≥≥
≥
100 Units
Range: 1 to 65000, Step 1
Range: 0.5 to 600.0, Step 0.5 s
Range: 0.5 to 600.0, Step 0.5 s
PULSE INPUT 3
DELAY: 10.0 s
PULSE INPUT 4
RELAY: OFF
PULSE INPUT 4
LEVEL
≥
≥≥
≥
100 Units
Range: 0.5 to 600.0, Step 0.5 s
PULSE INPUT 4
DELAY: 10.0 s
TOTALIZED PULSES
RELAY: OFF
TOTALIZED PULES
LEVEL
≥
≥≥
≥
100 Units
Range: 0.5 to 600.0, Step 0.5 s
TOTALIZED PULSES
DELAY: 10.0 s
Range: 1 to 65000, Step 1
Range: 1 to 65000, Step 1
Range: 0.5 to 600.0, Step 0.5 s
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 1 to 65000, Step 1
MESSAGE
MESSAGE
MESSAGE
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: ALARM, AUX1, AUX2,
AUX3, OFF