GE Power Management PQM Power Quality Meter 4-31
4 PROGRAMMING 4.3 S2 SYSTEM SETUP
4
4.3.6 PULSE INPUT
Figure 4–19: SETPOINTS PAGE 2 – SYSTEM SETUP / PULSE INPUT
•
PULSE INPUT UNITS:
This message allows the user to input a user defined 10 character alphanumeric
unit for the pulse inputs (i.e. kWh). The unit will be used by all pulse inputs including the totalized value.
To enter the unit, perform the following steps:
1. Allow access to setpoints by enabling setpoint access.
2. Select the
PULSE INPUT UNITS
message under the subgroup
S2 SYSTEM SETUP \ PULSE INPUT
.
3. Use the and keys to change the blinking character over the cursor. A space is
selected like a character.
4. Press the
key to store the character and advance the cursor to the next position. To skip over
a character press the key.
5. Continue entering characters and spaces until the desired message is displayed. If a character is
entered incorrectly, press the key repeatedly until the cursor returns to the position of the
error, and re-enter the character.
]] SETPOINTS
]] S2 SYSTEM SETUP
]] SETPOINTS
]] S3 OUTPUT RELAYS
SETPOINT
] CURRENT/VOLTAGE
] CONFIGURATION
] PULSE OUTPUT
]
PULSE INPUT UNITS:
Units
PULSE INPUT 1 VALUE:
1 Units
Range: 10 alphanumeric characters
PULSE INPUT 2 VALUE:
1 Units
PULSE INPUT 3 VALUE:
1 Units
PULSE INPUT 4 VALUE:
1 Units
PULSE INPUT TOTAL:
1+2+3+4
Range: 0 to 65000; Step: 1
] PULSE INPUT
]
Range: 1+2, 1+3, 1+4, 2+3, 2+4,
3+4, 1+2+3, 1+3+4,
1+2+4, 1+2+3+4
Range: 0 to 65000; Step: 1
Range: 0 to 65000; Step: 1
Range: 0 to 65000; Step: 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
VALUE VALUE
STORE
STORE
STORE