GE Power Management PQM Power Quality Meter 8-1
8 DNP COMMUNICATIONS 8.1 DNP 3.0 PROTOCOL
8
8 DNP COMMUNICATIONS 8.1 DNP 3.0 PROTOCOL 8.1.1 DEVICE PROFILE DOCUMENT
The communications port configured as a DNP slave port must support the full set of features listed in the
Level 2 DNP V3.00 Implementation (DNP-L2) described in Chapter 2 of the subset definitions.
DNP 3.0
DEVICE PROFILE DOCUMENT
Vendor Name: General Electric Power Management Inc.
Device Name: PQM Power Quality Meter
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
none
Maximum Data Link Frame Size (octets):
Transmitted: 249
Received: 292
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
None
Fixed
Configurable
Maximum Application Layer Re-tries:
None
Configurable
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable
Requires Application Layer Confirmation:
Never
Always
When reporting Event Data
When sending multi-fragment responses
Sometimes
Configurable
Timeouts while waiting for:
Data Link Confirm None Fixed Variable Configurable
Complete Appl. Fragment None Fixed Variable Configurable
Application Confirm None Fixed Variable Configurable
(fixed value is 5000 milliseconds)
Complete Appl. Response None Fixed Variable Configurable
Others: (None)