4-4 PQM Power Quality Meter GE Power Management
4.2 S1 PQM SETUP 4 PROGRAMMING
4
4.2.3 SETPOINT ACCESS
Figure 4–3: SETPOINTS PAGE 1 – PQM SETUP / SETPOINT ACCESS
To enable setpoint access, follow the steps outlined in the diagram below:
The factory default access code for the PQM is 1.
If three attempts are made to enable setpoint access with an incorrect code, the value of the
SETPOINT ACCESS
setpoint changes to
DISABLED
and the above procedure must be repeated.
]] SETPOINTS
]] S1 PQM SETUP
] SETPOINT ACCESS
]
SETPOINT ACCESS:
DISABLE
ENTER SETPOINT
ACCESS CODE: 0
SETPOINT ACCESS ON
FOR: 5 min.
CHANGE SETPOINT
ACCESS CODE: NO
]] SETPOINTS
]] S2 SYSTEM SETUP
SETPOINT
Range: DISABLE, ENABLE
Range: 1 to 999
Step: 1
] PREFERENCES
]
ENTER NEW ACCESS
CODE: 0
RE-ENTER NEW ACCESS
CODE: 0
ENCRYPTED ACCESS
CODE: 376
Range: 1 to 300 min. or UNLIMITED
Step: 1
Range: NO, YES
Range: 1 to 999
Step: 1
Range: 1 to 999
Step: 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
SETPOINT ACCESS:
ENABLE
ENTER SETPOINT
ACCESS CODE: 1
SETPOINT ACCESS ON
FOR: 5 min.
SETACCEN.VSD
INCORRECT CODE
CORRECT
CODE
INCORRECT
CODE
STORE STORE