Connecting Signal Cables for the Intelligent rPDU
8.7
Verifying the Installation
Item Check That Check Result
Indoor fan The fan is secured. The fan has no foreign matter inside.
□ Passed
□ Failed
Wet film
humidifier
(optional)
The water inlet solenoid valve, humidifier water pump, and wet film
are secured.
□ Passed
□ Failed
Outdoor
unit
The outdoor unit is secured. The outdoor unit air intake and exhaust
vents are not blocked. The outdoor unit installation meets
requirements.
□ Passed
□ Failed
Pipe
Pipe connectors are correct. The refrigerant pipes are tilted and
supported. The hose clamps and cable ties of the drainpipe are
secured. The refrigerant pipes and water pipes are wrapped with
thermal insulation foam. All pipes have been checked for leaks.
Water pipe joints have been sealed by sealant. The water inlet pipe
and drainpipe also have been checked for leaks. All pipes are not
bent by a large angle.
□ Passed
□ Failed
Cable
The input voltage is within the range of rated voltage ±10%, and
the input frequency is within the range of rated frequency ±3 Hz.
Cables are not damaged. All cables, connectors, and bolts are
secured. All cooling products are correctly grounded.
□ Passed
□ Failed
Cabinet
The cabinet layout position is consistent with the equipment room
layout diagram.
□ Passed
□ Failed
All bolts are tightened, especially the bolts used for electric
connection. Flat washers and spring washers are installed properly.
□ Passed
□ Failed
The cabinet is clear and complies with dustproof requirements.
□ Passed
□ Failed
All labels are correct, clear, and complete.
□ Passed
□ Failed