61
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose System Settings > Linkage Control.
3. Ensure that Enable linkage control function is Yes.
4. On the Linkage Group tab page, set Link fire control with Cabinet Electronic Clasp lock
open to on.
5. Modify the AI/DI_2 signal name为“消防”.
6. Enable the AI/DI device.
Linking the Fire Control with Cabinet Electronic Clasp Lock Open
3.14
FusionModule800 Linkage Control
Linking the Smoke Alarm with Cabinet Electronic Clasp Lock Open
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose System Settings > Linkage Control.
3. Ensure that Enable linkage control function is Yes.
4. On the Linkage Group tab page, set Link smoke alarm with Cabinet Electronic Clasp lock
open to on.
5. Modify the AI/DI_1 signal name为“烟雾”.
6. Enable the AI/DI device.
Linking the Emergency Ventilation with Cabinet Electronic Clasp Lock Open
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose System Settings > Linkage Control.
3. Ensure that Enable linkage control function is Yes.
4. On the Linkage Group tab page, set Link emergency ventilation with clasp lock open to
on.
High Humidity and Low Load Linkage Fan Dehumidification
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose System Settings > Linkage Control.
3. Ensure that Enable linkage control function is set to Yes.
4. On the Linkage Grouping tab page, set High humidity and low load linkage fan
dehumidification to on.
5. On the WebUI, choose Monitoring > ECC800 > Running Parameters > DO Control, change
the value of Signal Value from Normal open to Normal close, and click Submit.
6. Check whether the fan is running properly.
a) If the fan runs properly, the commissioning is successful. Change the value of Signal Value
fr
om Normal close to Normal open and click Submit to complete the commissioning.
b) If the fan does not run properly, contact technical support.