Item Check That Check Result
Cable
All cable joints are secured properly, especially the cable joints
between network cables.
□ Passed
□ Failed
Exposed parts near the wiring terminals and lugs are wrapped in
PVC insulation tape or heat shrinking tubing.
□ Passed
□ Failed
The flat washers and spring washers of all wiring terminals are
securely installed.
□ Passed
□ Failed
Cables are bound neatly and cable ties are secured evenly and
properly.
□ Passed
□ Failed
All labels at the cable ends are clear. □ Passed
□ Failed
Electrical
All ground cables are copper cables. Cable diameters are correct.
No switches or fuses are installed on the cables and no short circuit
occurs.
□ Passed
□ Failed
The ground cables, AC power cables, and internal cables are
correctly connected and screws are secured. No short circuit occurs
in power input or output.
□ Passed
□ Failed
The input voltage of smart cooling products is within the range of
rated voltage ±10%, and the input frequency is within the range of
rated frequency ±3 Hz.
□ Passed
□ Failed
The length of ground cables and power cables is correct. □ Passed
□ Failed
Lugs for power cables and ground cables are welded or crimped
securely.
□ Passed
□ Failed
Power cables and ground cables are routed and bundled separately
from other cables.
□ Passed
□ Failed
Lithium batteries are free of damage, cracks, and bulge. □ Passed
□ Failed
Lithium batteries are clear and experience no leakage. □ Passed
□ Failed
Wiring terminals of Lithium batteries are free of damage, break,
and acid leakage.
□ Passed
□ Failed
Lithium batteries safety valves remain intact and experience no acid
leakage.
□ Passed
□ Failed
Lithium batteries are connected correctly. □ Passed
□ Failed
DIP switches on devices are correctly set. □ Passed
□ Failed