Troubleshooting and fault elimination
Fault messages
Reset fault messages (TRIP−RESET)
11
246
EDBCSXS064 EN 4.0
11.3.2 Reset fault messages (TRIP−RESET)
Reaction Measures to reset the fault message
TRIP/ FAIL−QSP
Note!
If a TRIP/FAIL QSP source is still active, the pending TRIP/FAIL QSP cannot be reset.
The TRIP/FAIL QSP can be reset by:
l pressing ð 2 on keypad XT EMZ9371 BC. Then, press 1 to re−enable the controller.
l Set code C0043 = 0.
l Control word C0135, bit 11
l Control word AIF
l Control word system bus (CAN) / MotionBus (CAN) at ECSxS/P/M
After the reset of the TRIP/FAIL QSP, the drive remains at standstill.
Message
Danger!
The fault message is reset automatically after the fault has been eliminated, and the drive
restarts automatically.
Warning After the fault has been eliminated, the fault message is reset automatically.