441
Error Log Section 8-6
8-6 Error Log
The error log function registers the error code of any fatal or non-fatal error
that occurs in the PC. The date and time at which the error occurred are regis-
tered along with the error code. Refer to page 437 for error codes.
CQM1 Error Log Area In CQM1 PCs, the error log is stored in DM 6569 through DM 6599.
If a Memory Cassette without a clock is mounted, the date and time will be all
zeros.
Error records will be stored even if pin 1 on the CQM1 DIP switch is turned
ON to protect DM 6144 to DM 6655.
CPM1/CPM1A Error Log
Area
In CPM1/CPM1A PCs, the error log is stored in DM 1000 through DM 1021.
Error Log Storage Methods
The error log storage method is set in the PC Setup (DM 6655). Set any of the
following methods.
1,2,3... 1. You can store the most recent 10 error log records and discard older
records. This is achieved by shifting the records as shown below so that
the oldest record (record 0) is lost whenever a new record is generated.
2. You can store only the first 10 error log records, and ignore any subsequent
errors beyond those 10.
DM6569
Error log pointer
DM6570
Error log record 0
(3 words used.)
DM6571
DM6572
DM6597
Error log record 9
(3 words used.)
DM6598
DM6599
to
Error classification Error code
Min Sec
Day Hour
Leading word
Leading word + 1
Leading word + 2
Error classification: 00: Nonfatal
80: Fatal
Each stored in
2 digits BCD.
15 8 7 0
Each error log record is configured as follows:
Shows the number of error information items (0 to 7) stored in the
error log. "0" means that there are no items stored.
DM1000
Error log pointer
DM1001
Error log record 0
DM1002
DM1003
DM1019
Error log record 9
DM1020
DM1021
to
Error classification Error code
00 00
00 00
Leading word
Leading word + 1
Leading word + 2
The location for storing the next error record is shown. (0 to 6)
Error classification: 00: Nonfatal
80: Fatal
Bit 15 8 7
0
Each error log record is configured as follows:
Error log record 6
Error log record 7
Error log record 1
Error log record 2
Lost
New record added
All records shifted

Table of Contents

Other manuals for Omron CPM1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CPM1 and is the answer not in the manual?

Omron CPM1 Specifications

General IconGeneral
BrandOmron
ModelCPM1
CategoryController
LanguageEnglish

Related product manuals