Building Technologies Basic Documentation LMV27... CC1P7541en
21 Operating via AZL2 unit 17.12.2018
21.6.1 Backup
Parameter 000: flashes.
Display: Parameter 000: flashes, Int does not.
/
reset
Press to select parameter 050
Display: Parameter 050. flashes, index 00: and value 0 do
not.
/
reset
7548z358/1009
Press
reset
to select parameter bAC_UP
Display: Parameter bAC_UP
/
reset
Press
reset
to select the backup process.
Display: Value 0
Press
to shift the value in change mode 1 position to
the left.
Display: Value 1 flashes
Note
To detect potential display errors, the value is displayed 1
place shifted to the left.
/
reset
Press
reset
to activate the backup process.
Display: 1 appears