Building Technologies Basic Documentation LMV27... CC1P7541en
26 Parameter level 17.12.2018
26.7 Parameters without index, with direct display
26.7.1 Using the example of parameter 208: Program stop
PArAmeter level 200: for LMV27.
/
reset
Press
reset
to go to menu
level 200:
P
Vh
mi n
s%
Bild 64/0707
Press
to select Program stop.
Display: Parameter 208: flashes, value 0 does
not.
/
reset
P
Vh
mi n
s%
Bild 65/0707
Press
reset
to go to editing mode.
Display:
Program stop time set
Here: Value 0
corresponding to program stop deactivated
or
P
Vh
mi n
s%
Bild 66/0707
Press
or to select the required
program stop time.
0 = deactivated
1 = prepurge position (phase 24)
2 = ignition position (phase 36)
3 = interval 1 (phase 44)
4 = interval 2 (phase 52)
Example: 2 ignition position (phase 36)