153/219
Building Technologies Basic Documentation LMV27... CC1P7541en
26 Parameter level 17.12.2018
26.9 Parameter with index, with direct display
26.9.1 Using the example of parameter 501: No-flame positions fuel actuator
P
Vhmins%
Bild 75/0707
PArAmeter level 500: for fuel / air ratio
control.
reset
P
Vh
mi n
s%
Bild 76/0707
Press
reset
to go to menu level 500:.
Display: Parameter 501. flashes, index 00:
and value 0.0 do not.
reset
P
Vh
mi n
s%
Bild 77/0707
Press
reset
to go to the index.
Display: Parameter 501. does not flash, index
00: flashes, value 0.0 does not.
or
P
Vh
mi n
s%
Bild 78/0707
Press
or to select the required
index.
.00 = home position
.01 = prepurge position
.02 = postpurge position
Display: Index 01: for prepurge position
flashes, value 0.0 does not.
reset
P
V
h
mi n
s%
Bild 79/0707
Press
reset
to go to editing mode.
Display: Value 0.0
or
P
Vh
mi n
s%
Bild 80/0707
Press
or to select the required
prepurge position.
Example: 1.0