MP-3000 Controller
89
•“DEHUMITY VALVE
•“BYPASS VALVE
•“CAPACITY 100%
•“CAPACITY 50%
•“CAPACITY 25%
•“COMPRESSOR
b. Press F4 key to start the component test.
LCD display will change the component
state from off to on.
c. Verify component performance: LCD
display will show expected current and
actual current on phase 1, 2 and 3.
d. Press F4 key again to stop test. LCD
display will change component state from
on to off.
NOTE: Controller returns unit to normal
operation if no keys are pressed for 10
minutes. Pressing 5 key extends test time by
10 minutes each time it is pressed (maximum
time = 100 minutes). Pressing any other key
resets test time to 10 minutes.
6. System Test (test multiple components at the
same time):
a. Press F2 or F3 key to scroll to the first
component.
b. Press F4 key to turn the component on.
c. Press F3 key to scroll to select next
component. Press F4 key to turn
component on.
d. Repeat step 6c until all required
components are on. For example, to
operate unit in Full Cool mode, start the
following components:
Condenser Fan
Compressor
Capacity 100%
Evaporator High or Low
e. Observe current draw and system
performance to verify component(s)
performance.
f. Press F4 key again to turn off components
individually. Or press ESC key to exit
Manual Function Test menu and turn all
components off.
g. Press ESC key to exit the Manual
Function Test submenu.
NOTE: Controller returns unit to normal
operation if no keys are pressed for 10
minutes. Pressing 5 key extends test time by
10 minutes each time it is pressed (maximum
time = 100 minutes). Pressing any other key
resets test time to 10 minutes.
Power Management
Selecting a Power Limit from the Power Limit
screen turns on the power reduction control
algorithm that reduces total unit electric power
consumption based on the Power Limit and Power
Time settings.
With the U
NIT ON/OFF switch ON and the LCD
display showing the standard display (setpoint):
1. Press F3 key to enter the menu list.
Repeatedly press F2 key to scroll through
Main menu until COMMANDS appears in
LCD display.
2. Press F4 key to access the Commands menu.
The first command in the submenu (Defrost)
appears in the LCD display.
3. Press F2 or F3 key to scroll to POWER
MANAGEMENT.
4. Press F4 key to enter Power Management
submenu. LCD display shows the current
Power Limit setting and Power Time setting.
5. To activate or change the power limit:
a. Press F4 key with cursor in the POWER
LIMIT menu line. Cursor moves to end
of menu line and flashes.
b. Press F2 or F3 key to scroll to the desired
power limit setting: OFF, 13 amps,
15 amps or 17 amps.
c. With the desired power limit in the menu
line, press and hold F4 key until cursor
stops flashing. Cursor stops flashing and
new value appears in display.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thermo King CSR Series and is the answer not in the manual?

Thermo King CSR Series Specifications

General IconGeneral
BrandThermo King
ModelCSR Series
CategoryRefrigerator
LanguageEnglish

Related product manuals