MP-3000 Controller
93
6. When the desired text entry is complete, press
F4 key. Then press E
XIT key. The cursor stops
flashing and the new text appears in the menu
line.
7. Repeat steps 5 through 7 until all information
has been entered in the Cargo Data screen.
8. Press ESC key to exit the Cargo Data screen.
Changing the Temperature Display
Value (C/F)
1. Press the F3 key to enter the menu list. Press
F2 key to scroll to “MISC. FUNCTIONS”.
2. Press F4 key to access the Misc. Functions
menu. “DATE TIME” appears in the LCD
display. Press F2 key to scroll to “C/F
MODE”.
3. Press F4 key to access the C/F Mode screen.
C/F Mode screen appears with cursor in the
“TEMPERATURE VALUE” menu line.
Display shows “C/F MODE
o
C” where
C = Celsius and F = Fahrenheit.
4. To change the temperature value, press F4
key. Cursor moves to end of menu line and
flashes.
5. Press F2 key to toggle temperature value in
the menu line between “C” and “F”.
6. With the desired temperature value in the
menu line, press and hold F4 key until cursor
stops flashing. Cursor stops blinking and new
temperature value appears in display.
7. Press ESC key to exit the C/F Mode screen.
Configuration Menu
The Configuration menu displays a list of
functions that identifies unit operating features
and current settings. The following functions are
available: In-range, Container ID, Contrast,
Language, Economy Max, Economy Min.,
Humidity Option, Reefer Type, Zero Current,
Supply LH, AFAM Options, Evaporator Fans,
AFAM Setup, Auto Configuration and Serial
Number.
NOTE: When a spare parts controller is
installed and powered up for the first time, an
automatic configuration feature detects the unit
options installed on a unit. After the initial unit
power up, the controller turns the Auto
Configuration feature off. See “Replacing the
Controller” in this chapter for more
information.
Viewing or Setting Functions
With the UNIT ON/OFF switch ON and the LCD
display showing the standard display (setpoint):
1. Press the F3 key to enter the Main menu.
2. Press F2 key to scroll through Main menu
until “CONFIGURATIONS” appears in LCD
display.
3. Press F4 key to access the Configurations
screen. Configurations screen appears with
cursor in the “IN-RANGE” menu line.
4. Press F3 key to scroll cursor to view or reset
the desired function:
•“IN-RANGE”: Sets the temperature value
for the controller’s In-range LED and
datalogger functions (factory default = 1.5
C [2.7 F]). Enter a value from 0.5 to 5.0 C
(0.9 to 8.9 F).
•“CONTAINER ID”: Sets the container
identification number. Enter up to 11
characters (numbers or letters).
•“CONTRAST”: Controller automatically
regulates black and white contrast value
on LCD display according to display
temperature. Standard setting is 45.
Resetting this value is not recommended.