Configuring outputs
CNT-SVP01C-EN 29
4. If you want to edit the output name, highlight the text and type a new
name.
Use a descriptive name because it appears in custom displays and
programs.
5. Under Output Definition, type descriptors for the open and closed
states of the binary output.
Use descriptive terms because they appear on the operator display
and the Rover status displays.
6. Under On/Off Times, type the minimum on and off times.
The minimum off time is the least amount of time the output must be
off before it can go to on. The minimum on time is the least amount of
time the output must be on before it can go to off.
7. Complete one of the following options:
Click another output name in the Name list to edit another out-
put.
Click another tab to set up another item.
Click the Download button to send your changes to the Tracer
MP580/581. (If the Security Logon dialog box appears, log on.)
Click Close to close the Configuration dialog box.
Configuring analog outputs
You can name an analog output, specify its type, display its units and
numeric format, and perform calibration.
To set up an analog output:
1. In the Active Device View, click the AOs tab. The status information
for the analog outputs appears.
2. Click the Configuration button. The Configuration dialog box appears
with the AOs tab displayed (Figure 23 on page 30).

Table of Contents

Other manuals for Trane Tracer MP580

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer MP580 and is the answer not in the manual?

Trane Tracer MP580 Specifications

General IconGeneral
BrandTrane
ModelTracer MP580
CategoryController
LanguageEnglish

Related product manuals