3.8 External Interlock
102 YASKAWA SIEPC71061753C GA500 Technical Manual
3.8 External Interlock
For applications that will have unwanted effects on the system if the drive stops, make an interlock between
MFDO terminals set to H2-xx = E [MFDO Function Selection = Fault] and H2-xx = 6 [Drive Ready].
Drive ready
When the drive is operating or is prepared to accept a Run command, the MFDO terminal to which Drive Ready
[H2-xx = 6] is set will activate.
In these conditions, Drive Ready is OFF and the drive ignores Run commands:
The drive is de-energized
During a fault
There is problem with the control power supply
There is a parameter setting error that will not let the drive run, although a Run command is entered
An overvoltage or undervoltage fault occurs when the Run command is entered
The drive is in Programming Mode.
Interlock Circuit Example
Refer to Figure 3.53 for an example of how two drives that run one application use the Drive Ready and Fault
output signals to interlock with the controller.
Terminal Output Signal Parameter Settings for Output Signal
MA, MB, MC Fault H2-01 = E
P1-C1 Drive ready H2-02 = 6
Figure 3.53 Interlock Circuit Example

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals