Specifications
10
10.5 Model Specifications (Three-Phase 400 V Class)
YASKAWA SIEPC71061753C GA500 Technical Manual 335
10.5 Model Specifications (Three-Phase 400 V Class)
Table 10.7 Ratings (Three-Phase 400 V Class)
Model Duty Rating 4001 4002 4004 4005 4007 4009 4012
Maximum Applicable Motor
Output
*1
(kW)
HD 0.37 0.55 1.1 1.5 2.2 3.0 4.0
ND 0.37 0.75 1.5 2.2 3.0 4.0 5.5
Maximum Applicable Motor
Output
*1
(HP)
HD 1/2 3/4 2 3 3 4 5
ND 1/2 1 2 3 4 5 7.5
Input
Rated Input
Current (A)
HD (AC) 1.2 1.8 3.2 4.4 6.0 8.2 10.4
HD (DC)
1.5 2.2 3.9 5.4 7.3 10 12.7
ND (AC) 1.2 2.1 4.3 5.9 8.1 9.4 14
ND (DC)
1.5 2.6 5.3 7.2 9.9 11.5 17.1
Output
Rated Output
Capacity
*2
(kVA)
HD 0.9 1.4 2.6 3.7 4.3 5.6 7
ND 0.9 1.6 3.1 4.1 5.4 6.8 9.1
Rated Output
Current (A)
HD 1.2 1.8 3.4 4.8 5.6 7.3 9.2
ND 1.2 2.1 4.1 5.4 7.1 8.9 11.9
Overload Tolerance
HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.
ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.
Note:
Derating can be necessary for applications that start and stop frequently.
Carrier Frequency
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
V/f, OLV, OLV/PM: 590 Hz
AOLV/PM: 270 Hz
EZOLV: 120 Hz
Measures for
Harmonics
DC reactor External options
Braking Device Braking Transistor Standard internal characteristics
EMC Filter
EMC Filter
IEC61800-3
Factory option
Models 4xxxE: Category C2 (Conducted emission)
Power Supply
Rated Voltage/Rated Frequency Three-phase AC power supply 380 V to 480 Vat 50/60 Hz
Permitted Voltage Fluctuation -15% to +10%
Permitted Frequency Fluctuation ±5%
Input Power
(kVA)
HD
1.1 1.6 2.9 4 5.5 7.5 9.5
ND
1.1 1.9 3.9 5.4 7.4 8.6 13
*1 The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps must be equal to or more than the motor rated current.
*2 The rated output capacity is calculated with a rated output voltage of 440 V.
Table 10.8 Ratings (Three-Phase 400 V Class)
Model Duty Rating 4018 4023 4031 4038 4044 4060
Maximum Applicable Motor Output
*1
(kW)
HD 5.5 7.5 11.0 15.0 18.5 22.0
ND 7.5 11.0 15.0 18.5 22.0 30.0
Maximum Applicable Motor Output
*1
(HP)
HD 10 10 15 20 25 30
ND 10 15 20 25 30 40
Input
Rated Input
Current (A)
HD (AC) 15 20 29 39 50.5 59.7
HD (DC)
18.4 24.5 35.5 47.8 61.8 73.1
ND (AC) 20 24 38 44 59.7 80.7
ND (DC)
24.5 29.4 46.5 53.9 73.1 98.8

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals