7.6 Parameter Setting Errors
290 YASKAWA SIEPC71061753C GA500 Technical Manual
Code Name Causes Possible Solutions
oPE10 V/f Data Setting Error
The parameters that set the V/f pattern do not
satisfy these conditions:
For motor 1: E1-09 E1-07 < E1-06 E1-11
E1-04 [Minimum Output Frequency Mid Point
A Frequency < Base Frequency Mid Point B
Frequency Maximum Output Frequency]
For motor 2: E3-09 E3-07 < E3-06 E3-11
E3-04 [Minimum Output Frequency Mid Point
A Frequency < Base Frequency Mid Point B
Frequency Maximum Output Frequency]
Set the parameters correctly to satisfy the conditions.
Code Name Causes Possible Solutions
oPE11 Carrier Frequency Setting Error
These parameters are set at the same time:
C6-05 > 6 [Carrier Freq Proportional Gain >
6]
C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When C6-05 < 7, C6-04 becomes disabled. The
drive sets the carrier frequency to the value set
to C6-03.
C6-02 to C6-05 settings are not in the applicable
setting range.
Set C6-02 to C6-05 correctly.
Code Name Causes Possible Solutions
oPE13 Pulse Monitor Selection Error
H6-06 = 101, 102, 105, or 116 [Terminal MP
Monitor Selection = Frequency Reference, Output
Frequency, Motor Speed, Output Frequency after
Soft Starter] has not been set when H6-07 = 0
[Terminal MP Frequency Scaling = 0 Hz].
Set H6-06 correctly.
Code Name Causes Possible Solutions
oPE16 Energy Saving Constants Error
The Energy Saving parameters are not set in the
applicable setting range.
Make sure that E5-xx is set correctly as specified by the motor
nameplate data.
Code Name Causes Possible Solutions
oPE33 Digital Output Selection Error
These two parameters are set at the same time:
H2-60 F [Term MA,MB,MC Secondary
Function Not Used]
H2-01 = 1xx [Term MA,MB,MC Function
Selection = Inverse output of xx]
These two parameters are set at the same time:
H2-63 F [Terminal P1 Secondary Function
Not Used]
H2-02 = 1xx [Term P1 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
H2-66 F [Terminal P2 Secondary Function
Not Used]
H2-03 = 1xx [Term P2 Function Selection =
Inverse output of xx]
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
If you use the function to output logical calculation results
(H2-60, H2-63, H2-66 F), you cannot set H2-01 to H2-03 =
1xx.
These parameter pairs are set incorrectly:
H2-21 [Comparator 1 Lower Limit] > H2-22
[Comparator 1 Upper Limit]
H2-27 [Comparator 2 Lower Limit] > H2-28
[Comparator 2 Upper Limit]
Set parameters H2-21 H2-22.
Set parameters H2-27 H2-28.

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals