12.8 H: Terminal Function Selection
654 YASKAWA SIEPC71061753C GA500 Technical Manual
H2-61: Term MA,MB,MC Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-61
(1B47)
Expert
Term MA,MB,MC Logical
Operation
Sets the logical operation for the functions set in H2-01 [Term MA,MB,MC Function Selection]
and H2-60 [Term MA,MB,MC Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 647 for more information about the relation between parameter settings
and logical operations.
H2-62: Term MA,MB,MC Minimum ON Time
No.
(Hex.)
Name Description
Default
(Range)
H2-62
(1B48)
Expert
Term MA,MB,MC
Minimum ON Time
Sets the minimum ON time that the drive uses to output the logical calculation results from
terminal MA/MB-MC.
0.1 s
(0.0 - 25.0 s)
H2-63: Terminal P1 Secondary Function
No.
(Hex.)
Name Description
Default
(Range)
H2-63
(1B49)
Expert
Terminal P1 Secondary
Function
Sets the second function for terminal P1-C1. Outputs the logical calculation results of the
terminals set to functions by H2-02 [Term P1 Function Selection].
F
(0 - FF)
H2-64: Terminal P1 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-64
(1B4A)
Expert
Terminal P1 Logical
Operation
Sets the logical operation for the functions set in H2-02 [Term P1 Function Selection] and H2-63
[Terminal P1 Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 647 for more information about the relation between parameter settings
and logical operations.
H2-65: Terminal P1 Minimum ON Time
No.
(Hex.)
Name Description
Default
(Range)
H2-65
(1B4B)
Expert
Terminal P1 Minimum ON
Time
Sets the minimum ON time used to output the logical calculation results from terminal P1-C1.
0.1 s
(0.0 - 25.0 s)
H2-66: Terminal P2 Secondary Function
No.
(Hex.)
Name Description
Default
(Range)
H2-66
(1B4C)
Expert
Terminal P2 Secondary
Function
Sets the second function for terminal P2-C2. Outputs the logical calculation results of the
terminals assigned to functions by H2-03 [Term P2 Function Selection].
F
(0 - FF)
H2-67: Terminal P2 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-67
(1B4D)
Expert
Terminal P2 Logical
Operation
Sets the logical operation for the functions set in H2-03 [Term P2 Function Selection] and H2-66
[Terminal P2 Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 647 for more information about the relation between parameter settings
and logical operations.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals