Parameter Details
12
12.8 H: Terminal Function Selection
YASKAWA SIEPC71061753C GA500 Technical Manual 679
Figure 12.99 Analog Output Gain/Bias Configuration Example 2
Calibrate Terminal AM
Stop the drive to calibrate meters. Use this procedure to calibrate:
1. Show H4-02 [Terminal AM Analog Output Gain] on the keypad.
Terminal AM outputs the analog signal when the monitor item that you set in H4-01 [Terminal AM Analog
Output Select] is 100%.
2. Adjust H4-02 while referencing the meter scale connected to terminal AM.
3. Show H4-03 [Terminal AM Analog Output Bias] on the keypad.
The analog signal at the time when the monitor item selected with H4-01 is 0% is output from terminal AM.
4. Adjust H4-03 while referencing the meter scale connected to terminal AM.
H4-01: Terminal AM Analog Output Select
No.
(Hex.)
Name Description
Default
(Range)
H4-01
(041D)
Terminal AM Analog
Output Select
Sets the monitoring number to be output from the MFAO terminal AM.
102
(000 - 999)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02 [Output Frequency].
Note:
You cannot use all of the monitors in all of the control methods.
When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal AM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
H4-02: Terminal AM Analog Output Gain
No.
(Hex.)
Name Description
Default
(Range)
H4-02
(041E)
RUN
Terminal AM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
100.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of 10 V (or 20 mA). Use H4-07 [Terminal AM
Signal Level Select] to set the signal level.
H4-03: Terminal AM Analog Output Bias
No.
(Hex.)
Name Description
Default
(Range)
H4-03
(041F)
RUN
Terminal AM Analog
Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of 10 V (or 20 mA). Use H4-07 [Terminal AM
Signal Level Select] to set the signal level.
H4-07: Terminal AM Signal Level Select
No.
(Hex.)
Name Description
Default
(Range)
H4-07
(0423)
Terminal AM Signal Level
Select
Sets the MFAO terminal AM output signal level.
0
(0, 2)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals