Parameter Details
12
12.9 L: Protection Functions
YASKAWA SIEPC71061753C GA500 Technical Manual 733
L8-29: Output Unbalance Detection Sel
No.
(Hex.)
Name Description
Default
(Range)
L8-29
(04DF)
Output Unbalance
Detection Sel
Sets the function to detect LF2 [Output Current Imbalance].
1
(0, 1)
This function prevents damage to PM motors. Current unbalance can heat a PM motor and demagnetize the
magnets. When the current is unbalanced, the drive will detect LF2 to stop the motor and prevent damage to the
motor.
0 : Disabled
1 : Enabled
Note:
You must set E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)] and A1-02 = 8 [EZOLV] to show L8-29.
L8-31: LF2 Detection Time
No.
(Hex.)
Name Description
Default
(Range)
L8-31
(04E1)
LF2 Detection Time
Sets the LF2 [Output Current Imbalance] detection time.
3
(1 100)
When the output current is unbalanced for longer than the time set in L8-31, the drive detects LF2.
Note:
Set L8-29 = 1 [Output Unbalance Detection Sel = Enabled] to enable L8-31.
If the drive incorrectly detects LF2, increase L8-31 in 5-unit increments.
The keypad shows L8-31 when E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)] in EZ Vector Control.
L8-35: Installation Method Selection
No.
(Hex.)
Name Description
Default
(Range)
L8-35
(04EC)
Installation Method
Selection
Sets the type of drive installation.
0, 3
(0 - 3)
Note:
Parameter A1-03 [Initialize Parameters] does not initialize this parameter.
This parameter is set to the correct value when the drive is shipped. Change the value only in these conditions:
Side-by-Side installation
When you install a UL Type 1 kit on an IP20/UL Open Type drive to convert the drive to an IP20/UL Type 1 drive.
Mounting a standard drive with the heatsink outside the enclosure panel.
Do not change the settings for finless-type drives.
The drive automatically adjusts the overload protection detection level to the best value for each setting value.
Refer to Derating Depending on Ambient Temperature on page 342 for information about derating as specified by
ambient temperature.
0 : IP20/UL Open Type
Use this setting to install IP20/UL Open Type drives.
Make sure that there is 30 mm (1.18 in) minimum of space between drives or between the drive and side of the
enclosure panel.
1 : Side-by-Side Mounting
Use this setting to install more than one drive side-by-side.
Note:
You cannot install finless-type drives side-by-side.
2 : IP20/UL Type1
Use this setting to install IP20/UL Type 1 drives.
Note:
You cannot install an IP20/UL Type 1 Kit (optional) on a finless-type drive.
3 : External Heatsink/Finless
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals