Frame
size
NoiseAir flow
Typical power loss
1)
Type
ACS380-
04xx-…
dB(A)CFMm
3
/hBTU/hW
R16333572126204A0-4
R16333573119105A6-4
R163335734110007A2-4
R163335747814009A4-4
R259376356316512A6-4
R3667512888425917A0-4
R36675128133139025A0-4
R469881501351396032A-4
R469881501696497038A-4
R469881501986582045A-4
R469881502293672050A-4
1)
Typical drive losses when it operates at 90% of the motor nominal frequency and 100% of the drive nominal
output current.
Typical power cable sizes
The table in this section gives the typical power cable and conductor sizes for use at
the nominal drive current.
Note: IEC/EN 61800-5-1 requires two separate PE (ground) conductors for a fixed
connection, if the cross-sectional area of the PE conductor is less than 10 mm
2
Cu.
Frame
size
Conductor size, Cu (AWG)
Cable size, Cu (mm
2
)
1)
Type
ACS380-
04xx-…
1-phase U
N
= 230 V
R0163×1.5 + 1.502A4-1
R0163×1.5 + 1.503A7-1
R1163×1.5 + 1.504A8-1
R1163×1.5 + 1.506A9-1
R1163×1.5 + 1.507A8-1
R2143×2.5 + 2.509A8-1
R2143×2.5 + 2.512A2-1
3-phase U
N
= 230 V
R1163×1.5 + 1.502A4-2
R1163×1.5 + 1.503A7-2
R1163×1.5 + 1.504A8-2
R1163×1.5 + 1.506A9-2
R1163×1.5 + 1.507A8-2
R1143×2.5 + 2.509A8-2
146 Technical data